ARi Industries Inc.

RESISTANCE TEMPERATURE DETECTORS – RTDs

Resistance Temperature Detectors, also known as RTD’s, are wire wound and thin film devices which incorporate pure metals or certain alloys that increase in resistance as temperature increases and, conversely, decrease in resistance as temperature decreases. RTDs are similar to thermocouples in that they convert changes in temperature to voltage signals by the measurement of resistance. As a RTD gets hotter the resistance measured on it’s element becomes larger, as it cools the resistance becomes smaller.

Resistance Temperature Detectors

SPECIFICATIONS

SELECTION / MATCHING

Completed probes may be matched in pairs to the nearest 0.01 ohm at 0 °C for differential temperature measurements to 0.05 °C

Completed probes may be supplied with selected ice point resistances within a narrow band to eliminate the need for compensation in indicating circuits.

ARi ARiDET® consists of a specially installed platinum resistance element completely encased in compacted metallic oxide insulation of high thermoconductivity to insure minimum temperature differential between the sensor surface and the element. Standard sensors have 3 constantan equi-resistance lead wires in the lead portion with compacted MgO insulation. Sheath material is 316 L ST/ST in fully annealed condition. Performance specifications are shown for the element portion and the lead portion.

SPECIFICATIONS

SELECTION / MATCHING

Completed probes may be matched in pairs to the nearest 0.01 ohm at 0 °C for differential temperature measurements to 0.05 °C

Completed probes may be supplied with selected ice point resistances within a narrow band to eliminate the need for compensation in indicating circuits.

ARi ARiDET® consists of a specially installed platinum resistance element completely encased in compacted metallic oxide insulation of high thermoconductivity to insure minimum temperature differential between the sensor surface and the element. Standard sensors have 3 constantan equi-resistance lead wires in the lead portion with compacted MgO insulation. Sheath material is 316 L ST/ST in fully annealed condition. Performance specifications are shown for the element portion and the lead portion.

RTD
 LEADELEMENT
Accuracy ± 0.01 Ω at 0 °C  
Stability*-130 to 93 °C ± 0.05%  -130 to 315 °C ± 0.10%315 to 600 °C ± 0.50% 
Temp Range-250 to 1000 °C-200 to 600 °C    
Measuring Current 10 milliamps DC max    
Vibration ShockVibration:  ± 50G, 60 to 2000 Hz
Shock:  1000G
Along all three mutually perpendicular axes when correctly mounted.
Temp/Res. Curve —0.00385 Ω / Ω / °C per DIN 43760 0.003916 Ω / Ω / °C per JIS C 1604-81  
Individual Calib.  To nearest ± 0.01 Ω at °C  
Self Heating Error Less than 0.02 °C/MW  
Max External Pressure50,000 psi (3510 Kg/cm²)
Stock Length L24 inches (610 mm)

*Maximum ice point shift after long term thermal cycling.

SENSOR PARAMETERS
 1/8″3/16″1/4″
inchmminchmminchmm
Diameter0.1253.180.1884.780.2506.35
Temp. Sensitive Length1.128.01.128.01.128.0
Bending Restriction, Distance from tip to be left straight2.153.32.153.32.153.3
Minimum Bending Radius0.512.70.7519.01.025.4
Maximum Length700 ft213 m300 ft91 m175 ft53 m
Minimum Length410241024102
Constantan 3-Wire Leads, Resistance in Ω/in each wire0.0610.0250.015

TYPICAL 3-WIRE MEASURING CIRCUIT FOR RTD’S

A 3-wire system may be used to eliminate the effect of lead wire resistance changes by introducing RL (lead wire resistance) into each leg of the bridge. The third lead wire is added to the detector circuit without effecting bridge balance. The resultant circuit is sensitive only to resistance element temperature changes.

TYPICAL 3-WIRE MEASURING CIRCUIT FOR RTD’S

A 3-wire system may be used to eliminate the effect of lead wire resistance changes by introducing RL (lead wire resistance) into each leg of the bridge. The third lead wire is added to the detector circuit without effecting bridge balance. The resultant circuit is sensitive only to resistance element temperature changes.

TIME RESPONSE CHARATERISTICS

The response of an ARi Resistance Temperature Detector is defined by 2 noticable characteristics when exposed to an instantaneous (step) change in enviroment temperature. These are:

A.) Time Constant (tau). The time to reach 63.2% of the complete step change in temperature.
B.) Response Time. Time to reach within 0.5% of the final temperature in a step change.
This is approximately equal to 5 times the time constant

The response of a temperature sensor to a step change in environment temperature tends to follow a second order differential equation. However, this is approximate, since if the mass of the sensor is small in relation to the mass of the fluid passing over it (such as in the case of a liquid), the response may approach a first order differential equation. A typical response is as follows:

Time constant has application for more common experiences in process control, ie, ramp change or sinusoidal changes in enviromental temperature. The response of a sensor under these conditions are:

TIME RESPONSE CHARATERISTICS

The response of an ARi Resistance Temperature Detector is defined by 2 noticable characteristics when exposed to an instantaneous (step) change in enviroment temperature. These are:

A.) Time Constant (tau). The time to reach 63.2% of the complete step change in temperature.
B.) Response Time. Time to reach within 0.5% of the final temperature in a step change.
This is approximately equal to 5 times the time constant

The response of a temperature sensor to a step change in environment temperature tends to follow a second order differential equation. However, this is approximate, since if the mass of the sensor is small in relation to the mass of the fluid passing over it (such as in the case of a liquid), the response may approach a first order differential equation. A typical response is as follows:

Time constant has application for more common experiences in process control, ie, ramp change or sinusoidal changes in enviromental temperature. The response of a sensor under these conditions are:

Time constant is related to the environmental conditions by the following approximate relation (Ref NASA TN 2599)

Knowing the time constant for a given sensor at one given set of conditions, it can be computed for another set of conditions.

Time constant is related to the environmental conditions by the following approximate relation (Ref NASA TN 2599)

Knowing the time constant for a given sensor at one given set of conditions, it can be computed for another set of conditions.

MODEL’S AND DESCRIPTIONS

Calibration

All assemblies shown can be supplied with a different calibration and 0°C resistance value.

Calibration Ω / Ω / °CARi Symbol
0.00385100 DIN
0.003916100
Lengths

Standard lengths for the 3 diameters is 24″ (610mm). Longer lengths of compacted MgO insulated lead portion can be supplied up to the following.

DiameterMaximum Length
(inch)(mm) (feet)(meters)
0.1253.18 700213
0.1884.78 30091
0.2506.35 17553

Duplex elements at 0.250″ diameter will be approximately the same length.

Duplex Elements

Can be supplied at 0.250″ diameter only where suitable terminations can be made. Temperature transmitters for duplex circuits are not available for internal mounting in connection heads. The following styles can be made with duplex elements. Specify the 6 wire style for duplex elements.

Number Of WireBare WireExtension WireStandard Size Connection HeadHinged Cover Connection HeadNylon Connection Head
3-Wire StylePRT-14.3PRT-22.3PRT-96.3PRT-296.3PRT-396.3
6-Wire StylePRT-14.6PRT-22.6PRT-96.6PRT-296.6PRT-396.6
Single Circuit 4 Wire

PRT Type assemblies can be made with four (4) leadwires with the following circuit.

*Send us your drawings/sketches for prompt quotations.

How To Order
  • Establish Part Number:

RTD008

  • Specify quantity and any special tests.
  • Specify installation accessories and quantity.
  • If temperature is required to produce 4-20ma with 28VDC excitation, use Style PRTX.

ACCESSORIES

Please contact us for further information or any special requirements you may have.

Standard AerOpak® Mineral Insulated Cable is normally available from our inventory for immediate shipment. Call or email for details!